Cooling

Why air stops

Moving heat with air needs airflow and fan power that become impractical above roughly 20 to 30 kW per rack. NVL72-class racks cool GPUs and CPUs with liquid, but power supplies, NICs and some switches still reject heat to air, so every liquid-cooled hall keeps some air handling.

Source: https://pantheon.run/learn/nvidia-gb200-nvl72-power-and-cooling Checked 2026-09-18

FigureValueSource
Practical air ceiling20 to 30 kW per rackhttps://www.vertiv.com/en-ca/insights/articles/educational-articles/data-center-containment-strategies-for-high-density-environments/ checked 2026-10-06
Opened 2026-10-06: Vertiv's containment article gives 20-30 kW per rack for air-cooled rows. Re-sourced from pantheon.run, whose page carries no such figure. This is a vendor's rule of thumb, not a standard.
GB200 NVL72 rackNVIDIA reference rack about 120 kW; HPE's OEM configuration rated 132 kW nominal, about 192 kW peak design powerhttps://pantheon.run/learn/nvidia-gb200-nvl72-power-and-cooling checked 2026-09-18
GB300 NVL72 rack132 to 155 kW by configurationhttps://www.supercomputing.news/emerging/nvidia-45c-warm-water-cooling-mgx-data-center checked 2026-09-18
Liquid to air splitabout 115 kW liquid, 17 kW air (87 / 13 %)https://pantheon.run/learn/nvidia-gb200-nvl72-power-and-cooling checked 2026-10-07 unverified
Unsourced. The pantheon.run page cited here carries no liquid-to-air split. HPE's product page for the GB200 NVL72 was opened in a browser on 2026-10-07: it describes a mix of air and liquid cooling but gives no kW or percentage figures. The figure may be in HPE's QuickSpecs, which were not read.